Product Detailed
Related Categories:Uninterrupted Power Supply (UPS)
Related Product Searches:Online three phase uninterruptible power systems (120KVA),High Quality,uninterruptible power systems, on line ups power,HP12000
1.3 phases uninterruptible power systems,
2.120KVA,
3.High frequency,
4.With external battery bank,
5.EPO and Bypass.
Related Product Searches:Online three phase uninterruptible power systems (120KVA),High Quality,uninterruptible power systems, on line ups power,HP12000
Online three phase uninterruptible power systems
KEY FEATURES:
Online double conversion VFI provide pure sine ware.IGBT inverter and output isolation transformer improve the system efficiency and reliability for kinds of load: transformer, emergency light, electric facility, industry processes, etc.Parallel redundant, parallel up to 8 modules.Detect all the information and status showing on LCD.Intelligent RS232 Communication Port.Set output voltage from 220~240V.Over voltage, low voltage, over current, over load, etc can be detected and supply reliable protection. (EN/IEC60240)Advanced battery management.UPS monitoring software.Technical Parameters:
Model | HP12000 | |
Capacity | 120KVA | |
Output power factor | 100~70% | |
Efficiency(normal operating), load 100% | 93~95% | |
Efficiency(economic model ), load 100% | 98% | |
Maximum leakage(mA) | 100 | |
Mean time between failures(MTBF) | 200,000 hours | |
Remote signaling | 3 dry contact (battery low, battery discharge, bypass/failure);output 12Vdc 80mA | |
Remote control | EPO, bypass | |
Communication | RS232/C | |
Operating temperature | 0±40°C | |
Max relative humidity | 95%(non condensation) | |
Cool down | Mandatory wind( RPM change according to load ) | |
Altitude | 1KM output normal power( with increase of 100m, reduce 1%) Max 4KM | |
Noise | 60~65 dB | |
Protecting Standard(EN 60529) | IP20 | |
Incoming/outgoing cables | Downward/Back | |
Standard | Standard:GB4943; Battery combinations:GB7260.2, GB/T 17626.2~5 | |
Dimensions(W*D*H)mm | 1200*740*1400 | |
Weight(without battery)KG | 1020 | |
Rectifier input(standard UPS) | ||
Rated voltage | 380V,3 phases | |
Voltage range | ±20% | |
Rated frequency | 50/60Hz auto sensing | |
Frequency range | 45~65 | |
Maximum input current[A] | 220 | |
Power factor | 80% | |
Soft start | 0-100%,10 seconds | |
Battery | ||
Charge current setting | 0.5A*C10 | |
Units(Rated voltage ) | 216(432VDC) | |
Charge current setting | 0.2A*C10 | |
Inverter output | ||
Rated voltage[v] | 380(3 phase+N) | |
Rated current[A] | 186 | |
phase voltage | 220~380V(control pannel) | |
Waveform | Sine wave | |
(Ipeak/Lrms) | ||
Linear load wave distortion | <2% | |
Nonlinear load wave distortion | <5% | |
Voltage stability | ±1% | |
Transient voltage stability | ±5%(in 10ms) | |
Rated frequency | Same as input frequency | |
Overload | 600'/10'/1', (110/125/150% nominal current) | |
Inverter efficiency | 96% | |
Bypass | ||
Rated Voltage | 380 (3 phase +N) | |
Input voltage range | ±15% (Settled to ±10% or ±25% via control panel available) | |
Rated frequency | 50Hz/60Hz | |
Frequency range | ±2% (Settled to ±5% via control panel available) | |
Inverter/bypass transfer time | <1ms | |
Overload capacity | 10'/1'/18"(150/175/200% nominal current) |
Online three phase uninterruptible power systems (120KVA)